Diagnosis Methods For more information about troubleshooting, see the following views in CODESYS or external software, each depending on the case: Status dialog in the device configurator If the objec
PROFINET and Other Drivers The PROFINET Controller and Device require exclusive access to the low-level Ethernet component (SysEthernet). As a result, for example, they cannot run parallel with EtherC
PROFINET and Older Runtime Versions The PROFINET drivers require at least one runtime V3.5.7.0. For the Windows RTE runtime, at least V3.5.10.0 is recommended (problems regarding reserved UDP ports fr
Hardware Requirements PROFINET requires an Ethernet adapter that supports at least 100 mbps with full duplex. All applied network components (switches) also have to support this transmission mode. MAC
Effects and Causes Controller – Device object has a red symbol. It is imperative that you check the Controller status on the Status tab of the device. Causes The IP address or the station name of the
Error due to multiple IP addresses When the PROFINET Controller is started, it checks the network for duplicate IP addresses. The operation of establishing the connection can be aborted with the error
Notes about Certification The CODESYS PROFINET Controller and the CODESYS PROFINET Device are continuously checked against the currently valid versions of the PI Conformance Tests. However, a PROFINET
Device – General Object: PROFINET Device In this dialog, you configure a communication link ( PROFINET : application relation) to a PROFINET Field Device. For all settings in the present dialog, the d
Device – IOxS Object: PROFINET Device In this dialog, you can enable or disable the I/O provider data or I/O consumer status data of individual submodules. As a result, the status byte is also mapped
Device – State Object: PROFINET Device The tab displays the diagnostic data and the alarms of the device. Diagnosis Data The diagnostics currently located in the device. The current diagnostics data i